Skip to main content

Cutler-Hammer FH27 A200/B100 Heater Coil, 10 A, 1 Poles

Selected FH27Cutler-Hammer FH27 A200/B100 Heater Coil, 10 A, 1 Poles
FH27Cutler-Hammer FH27 A200/B100 Heater Coil, 10 A, 1 Poles

Documents

Short Description

Each heater is identified by a catalog number stamped on one terminal. The heater application table indicates the range of full load motor current to which a given heater may be applied. Heaters should be selected on the basis of the actual full load current and service factor as shown on the motor nameplate or in the manufacturer's published literature. When motor and overload relay are in the same ambient and the service factor of the motor is 1.15 to 1.25, select heaters from the heater application table. If the service factor of the motor is 1.0, or there is no service factor shown, or a maximum of 115% protection is desired, select one size smaller heater than indicated.

Features

  • 2.59 to 2.83, 3.00-3.28 A Ambient, 2.20-2.39, 2.67-2.92 A Non-compensated

Specification

Full Load Current Rating
2.59 to 2.83
Number Of Poles
1
Series
A200/B100
Size
0,1 and 2
Temperature Rating
40
Trip Type
Thermal and Fast Trip
Application
Safety and emergency exit devices
Standard & Approvals
CSA Certified, UL Listed
Enclosure Type
M-0 Enclosed/M-1 Enclosed
Amperage Rating
10 A

Call it Something Else?

Loading product details...